4 - COMPONENTS AND MAINTENANCE
4.8.2 - 230 V - Actuators
Two types of valve actuators are provided : electrothermal 
actuator (on/off control) or modulating actuator (3-point).
The actuator supply is 230 V a.c.
4.8.3 - 24 V - Actuators
Three  types  of  valve  actuators  are  provided  :  one 
electrothermal actuator (on/off control) or two modulating 
actuators (3-point or 0-10V).
Both modulating actuators can be operated manually
with  a  hexagonal  key.  The  0-10V  command  voltage 
range of the modulating actuator can also be adjusted.
The actuator supply is 24 V a.c.
NOTE: 24V actuators are not compatible with Carrier
controllers (Thermostats A/B/C/D, WTC & NTC).
4.8.4 - Actuator replacement procedure
The actuators on both the chilled water and the hot water 
valves may be replaced in case of failure.
WARNING : Do not connect on the same neutral wire
the valve actuator 24 Vac and the controller.
■ Disconnect  the  power  supply  to  the  unit  before 
carrying out any work on a unit.
■ Disconnect the actuator power supply cable.
- 230 V type actuator used with the Carrier numeric 
controller: Disconnect the actuator power supply 
cable fitted with a quick connector.
- 230 V actuator used with an electronic thermostat: 
Remove the plastic protection cover held in place
with two screws. Disconnect the actuator power 
supply cable connected to the quick connector.
This  can  be  done  by  pressing  down  the  spring 
tongue using a screwdriver and pulling out the wire 
from the appropriate terminal.
■ Uncouple the faulty actuator. Refitting is by the
reversal of the procedure described above.
WARNING: Ensure that the actuator is firmly
screwed to the valve body (maximum torque 15
N·m).
4.8.5 - Valve body replacement procedure
■ Disconnect the power supply before carrying out any 
work on a unit.
■ Close the isolating valves on the manifolds.
■ Unscrew  the  union  nuts  to  disconnect  the  flexible 
water pipes.
■ Remove the valve actuators taking care to identify
the cooling and heating valves.
■ Disconnect the flexible condensate drain pipe which 
is held in place by a collar (the collar is not supplied 
by Carrier).Remove the two-way or four-way water 
flow control valve bodies. Depending how the unit is 
configured, the four-way valve coupling may be fitted 
with  a  heating/cooling  changeover  switch,  if  so  do 
not remove it.
■ Fit the new valve body to the coil (fit new gaskets).
■ Reconnect the flexible condensate drain pipe which 
is held in place by a collar (the collar is not supplied 
by Carrier).
■ Refit the valve actuators taking care to ensure that 
they are correctly fixed to the valve body.
■ Reconnect the flexible water pipes by tightening the 
union nuts. Retighten all the water connections and 
ensure that all gaskets have been changed and
correctly fitted (maximum torque 15 N·m).
■ Open the isolating valves on the manifolds and purge
all air from the system.
■ Check that there are no leaks and reconnect the
power to the unit.
WARNING: When replacing a valve always ensure
that the direction of flow through the valve is as
shown by the arrow on the valve body. If the
direction of flow is wrong, the valve body will
deteriorate rapidly and the flow control will be
distorted.

4.9 - Flexible pipe option

Minimum bending radius:
■ Non-insulated pipes 72 mm
■ Insulated pipes 106 mm.
Connections for unit size 2, 3, 4 and 5: 1/2'' diameter 
(female)
Connections for unit size 6 and 7: 3/4'' diameter (female)
21