Functions
10.2.3

X.LIMIT -

Stroke limitation

This function limits the (physical) stroke to predetermined % values (bottom and top). The stroke range of
the limited stroke is thereby set to 100%. If the limited stroke range is exceeded during operation, negative
actual positions or actual positions greater than 100% are displayed.
Factory setting: Bottom stroke limitation= 0%, Top stroke limitation = 100%
Setting ranges:
Bottom stroke limitation:
Top stroke limitation:
The minimum distance between the bottom and top stroke limitation is 50%, i.e. when a value is entered
whose minimum distance is < 50%, the other values are automatically adapted.
Limited
Physical stroke
stroke (%)
(%)
Fig. 19:
Diagram X.LIMIT
0...50% of the total stroke
50...100% of the total stroke
Unlimited
stroke
Limited
stroke
Set-point
value [mA]
(INPUT)
english
47