10.2.2

SPLTRNG -

Signal split range

Minimum and maximum value of the input signal in % for which the valve runs through the whole stroke
range.
Factory setting: signal split range bottom = 0%; signal split range top = 100%
Signal split range bottom: I nput of the minimum value of input signal in %:
Signal split range top: I nput of the maximum value of the input signal in %
This function limits the position set-point value range of the positioner by setting a minimum and maximum
value. This makes it possible to split a used standard signal range (4...20 mA, 0...20 mA) into several positioners
(without or with overlap). In this way, several valves can be used alternately, or simultaneously for overlapping
set-point value ranges, as proportional valves.
Splitting of one standard signal range into two set-point value ranges:
Valve stroke [%]
Fig. 18:
SPLTRNG diagram
46
Setting range: 0...75%
Setting range: 25...100%
Set-point value
Set-point value
range
range
Positioner 1
Positioner 2
english
Type 8791, REV.2
Functions
Set-point
value [mA]
(INPUT)