Qualitrol INFORMA PMD-A User Manual page 232

Data acquisition unit
Table of Contents

Advertisement

Appendix G – On-Board Jumper Settings
Sl
Channel
No.
No./Purpose
CH9
User can configure the TX-AFE/ HIA-AFE board as TX-AFE/ HIA-AFE 1 or TX-
Note
AFE/ HIA-AFE 2 for INFORMA PMD-A 6U device, which means TX-AFE/ HIA-
AFE 1 relates to analog channels 1-9 and TX-AFE/ HIA-AFE 2 relates to
analog channels 10-18.
The following table lists the jumper settings while configuring TX-AFE/HIA-AFE as TX-
AFE/HIA-AFE1 orTX-AFE/HIA-AFE 2.
HIA-AFE Jumper Table
Channel
Jumper
Type
Legend
J160
J113
Voltage
J114
J111
Current
J112
J118
DC
Voltage
J119
225
Position
Selection
1-2
Mounted for
2-3
Input 140V
FSD
Mounted for
1-2
Input 270V
FSD
Mounted for
2-3
Input 480V
FSD
Mounted for
1-2
Input 800V
FSD
Mounted for
1-2
Input 10A FSD
Mounted for
2-3
Input 20A FSD
Mounted for
1-2
Input 50A FSD
Mounted for
2-3
Input 100A
FSD
Mounted for
1-2
Input 12VDC
FSD
Mounted for
2-3
Input 120VDC
FSD
Mounted for
1-2
Input 240VDC
FSD
Mounted for
2-3
Input 480VDC
FSD
Description
Voltage
Range
Selection
Current
Range
Selection
DC Voltage
Range
Selection
www.qualitrolcorp.com