Qualitrol INFORMA PMD-A User Manual page 107

Data acquisition unit
Table of Contents

Advertisement

Configuration
Figure 6.21 – PQ 10-Minute Continuous Recording
Free Interval Recordings
Minimum, Maximum, and Average values are calculated using data as per the
aggregation interval configured.
The user can configure the aggregation interval as 200 ms, 1 second, 2 seconds, 3
seconds, 6 seconds, 15 seconds, 30 seconds, and 1 minute to 1440 minutes.
For aggregation interval as 200 ms, 200 ms data is considered and the record will
contain only the average value.
200 ms data is aggregated for aggregation intervals of 1 second and 2 seconds.
3 seconds data is aggregated for aggregation intervals of 3 seconds, 6 seconds, 15
seconds, 30 seconds, and 1 minute to 30 minutes.
For an aggregation interval greater than 30 minutes, 10-minute data is aggregated.
The user can configure the PQ parameters to be recorded (limited to 256 parameters).
Output available will be Minimum, Maximum, and Average values for each of the
selected parameters for the entire duration.
100
www.qualitrolcorp.com