Qualitrol INFORMA PMD-A User Manual page 142

Data acquisition unit
Table of Contents

Advertisement

Maintenance
If any one or all three LEDs (Power healthy, Communication, and Clock Sync) on the front
panel of the INFORMA PMD-A device are not working, perform the steps mentioned in the
following table for finding the fault in the device and rectification.
Problem Symptom and
Indication
Not all the LEDs are
glowing.
Or
Only Power Healthy LED
is OFF and all other are
working.
No Communication –
Only COMMS LED is
OFF and all other LEDs
on the front panel are
working.
Clock sync LED is OFF
and all other LEDs on
the front panel are
working.
Potential Causes
Power Supply not
working
Motherboard not
working
Communication
modules not
working
Motherboard not
working
Not synchronized
with GPS/RTC
PPS (in master
mode)
Not synchronized
with external
master (in slave
mode)
Motherboard not
working
135
Corrective Action
Refer to Section 6.4.1 for
initial inspection and
rectification.
1. Ensure that the serial
port and connection
cable pin-out are
compatible.
2. Check the PC baud
rate.
Refer to Section 6.4.2 for
further probing
information
.
Refer to Section 6.4.3 for
initial inspection.
www.qualitrolcorp.com