Appendix A – Technical Specifications
Standards
and Interruptions
IEC 60255-22-2 / IEC 61000-4-2
Electro static discharge tests
IEC 60255-6/EN60255-6 Supply
voltage limit test
IEC 60068-2-1/EN60068-2-1 Cold tests
IEC 60068-2-6 Vibration tests
IEC 60068-2 Cyclic Temperature Test
References/Test criteria
Tested on Power-port.
Passed with : Dips - Criteria A
Interruptions - Criteria B
Tested to IEC 61000-4-2,Tested for : 8 kV
contact, 15 kV air
Tested on Enclosure, all accessible I/O lines
and ports.
Passed with : Criteria A
Tested for PSU Tested for DC range 80VDC
to 132VDC
Tested for Cold Storage -45˚C (49˚F) for 96
hours
Cold Operating: -5˚C (23˚F) for 16 hours
Tested on Complete Device
Tested for 2g Acceleration, Frequency is
10- 150 HZ, 20 sweep cycles in each of
three mutually perpendicular planes (x, y,
and z).
Tested on Complete Device
Tested for Cyclic Temperature test for a 5
cycles. Each cycle has 3 hours for 70
degrees & 3 hours for -5 degree in Power off
Condition
Tested on Complete Device