Qualitrol INFORMA PMD-A User Manual page 152

Data acquisition unit
Table of Contents

Advertisement

Appendix A – Technical Specifications
Standards
IEC 60255-22-4 / IEC 61000-4-4 &
ANSI C37.90.1.2002 Electrical fast
transient burst test
IEC 60255-22-3 / IEC 61000-4-3
Radiated Susceptibility (RS)
EN 55011 Conducted Emission (CE)
EN 55011 Radiated Emission (CE)
IEC 61000-4-8 Power frequency
magnetic field test
IEC 60255-22-1 / IEC 61000-4-12 &
ANSI C37.90.1.2002 Damped
oscillatory wave disturbance tests
References/Test criteria
Tested to IEC 61000-4-4, Tested for : 4 kV,
5KHz/100KHz/2.5KHz
Tested on Power-line, RS232-1, Ethernet
port 1, Analog inputs (V & I), Digital Inputs,
Relay outputs.
Passed with : Criteria A
Tested to IEC 61000-4-3, Tested for 10
V/m, 80 MHz – 1000 MHz
Tested on Complete Device
Passed with : Criteria A
Tested to CISPR-11 Tested for 79 dB (µV)
quasi-peak and 66 dB (µV) average at 0.15
MHz to 0.5 MHz
73 dB (µV) quasi-peak and 60 dB (µV)
average at 0.50 MHz to 5 MHz
73 dB (µV) quasi-peak and 60 dB (µV)
average at 0.50 MHz to 5 MHz
Tested on : Complete Device
Passed & the Emission levels are within the
Specified limits of CISPR 11
Tested to CISPR-11 Tested for 40 dB
(µV/m) quasi-peak from 30 MHz to 230 MHz
at 10 m (32.8 ft)
47 dB (µV/m) quasi-peak from 230 MHz to
1000 MHz at 10 m (32.8 ft)
Tested on : Complete Device
Passed & the Emission levels are within the
Specified limits of CISPR 11
Tested to IEC 61000-4-8 ,Tested for 30
A/m, x, y, z axis
Tested on : Complete Device
Passed with : Criteria A
Tested to IEC 61000-4-12 ,Tested for 2.5
kV Common Mode, 1 kV Differential Mode,
1MHz
Tested on : Power-line, Digital, Analog
145