Qualitrol INFORMA PMD-A User Manual page 219

Data acquisition unit
Table of Contents

Advertisement

Appendix G – On-Board Jumper Settings
Sl
Channel No
No.
/Purpose
CH9
AFE BOARD
11
SELECTION
External/
12
Internal CT
Selection
TX-AFE Jumper Table
Channel
Jumper
Type
Legend
J50
Voltage
J53
J68
Current
J64
TX-AFE/
J76-J89 2-3
HIA-AFE
1
TX-AFE/
HIA-AFE
J76-J89 1-2
2
J90-
For CT
J107
212
Position Selection
Channel
2-3
Configured
as Current
Mounted
2-3
for Input
140V FSD
Mounted
1-2
for Input
270V FSD
Mounted
2-3
for Input
480V FSD
Mounted
1-2
for Input
800V FSD
Mounted
1-2
for Input
10A FSD
Mounted
2-3
for Input
20A FSD
Mounted
1-2
for Input
50A FSD
Mounted
2-3
for Input
100A FSD
Board
configured
as TX-
AFE/HIA-
AFE 1
Board
configured
as TX-
AFE/HIA-
AFE 2
External
1-2
CT
2-3
Internal CT
Description
Default
Voltage
Range
Selection
Current
Range
Selection
www.qualitrolcorp.com