5.15 Programming the Control Panel and Annunciators

After annunciator installation is complete, program the fire alarm control panel to accept the annunciators as explained in the panel's pro-
gramming guide (see Section 1.3, "Related Documentation" for part numbers).
5.15.1 Selecting LED Colors: ACM-24AT and AEM-24AT
Steps to set color of a point-active LED:
1.
Power up system according to your control panel instructions.
2.
Set DIP switch SW32-1 to "on" to enter programming mode.
3.
For each point, press the rubber switch to cycle red/green/yellow and select color that is appropriate for the point's function (suggested:
red for alarm, yellow for trouble, green for active).
4.
Set DIP switch SW32-1 back to "off" to return to normal operation.
5.
Hold down the Acknowledge/Lamp Test switch to do a lamp test and verify color selections were set correctly.
5.15.2 Selecting LED Colors: ACM-48A & AEM-48A
Set SW31 to set color of the point-active LEDs in the right column, and SW30 to set color of the point-active LEDs in the left column. DIP
switches are located behind the column of LEDs they control.
To locate these switches on the back of the annunciator, refer to Figure 5.1 and Figure 5.2. To set a DIP switch "ON", push it towards the
green circuit board.

5.16 Testing the Annunciators

After programming, fully test the Annunciator Control System to ensure that each switch performs its intended function, that each LED
lights in the correct color, and that the annunciators can perform the functions outlined in this manual.
28
ACM-48A
LED
Switch
Position
No color
SW30-1 off
SW31-1 off
SW30-2 off
SW31-2 off
green
SW30-1 on
SW31-1 on
SW30-2 off
SW31-2 off
red
SW30-1 off
SW31-1 off
SW30-2 on
SW31-2 on
yellow
SW30-1 on
SW31-1 on
SW30-2 on
SW31-2 on
Programming the Control Panel and Annunciators
AEM-48A
Switch
Switch
Position
Position
SW25-1 off
SW25-2 off
SW25-1 on
SW25-2 off
SW25-1 off
SW25-2 on
SW25-1 on
SW25-2 on
Switch
Position
SW26-1 off
SW26-2 off
SW26-1 on
SW26-2 off
SW26-1 off
SW26-2 on
SW26-1 on
SW26-2 on