C.4 Configuring Annunciators for the AFP-300/AFP-400
The switch numbers given below are for SW28 on the ACM-24AT and ACM-48A, and for the 8-pin DIP switch on the ACM-16AT and
ACM-32A. Address and DIP switches must be set before the annunciator will operate properly. See Section 5.2 for switch locations.
Switch #
ACM-24AT and ACM-48A
1
Not used: This switch must be set "OFF"
2, 3
Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 for ACM-
24AT/ACM-48A; see Section 5.13.3 for ACM-16AT/ACM-32A.
4
Not used; set to OFF
5
Receive Only: Set this switch "ON" for each annunciator that will provide the same information as another annunciator in a different location.
(When two or more annunciators hold the same address, all but one must be configured as "Receive Only" annunciators.)
6
Piezo Disable: Set this switch "ON" to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is "ON".)
7
Switch Inhibit: Set this switch "ON" to disable the point control switches on the annunciator and prevent them from executing system control
functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will
function only in a local capacity unrecognized by the system.
NOTE: Only the first four switches control the AFP-300/AFP-400. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset,
4=Drill.
8
Flash Inhibit: Set this switch "ON" to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the
piezo from sounding.
1
See Sections 5.12.1 and 5.12.4 for details about SW32 on ACM-24AT and ACM-48A.
C.5 System and Point Annunciation
The control panel's annunciation points are divided into nine ACS Selection Groups of 64 points. Table C.1, which follows, summarizes the
ACS Selection Groups and what an annunciator displays if a group is selected. The AFP-300/AFP-400 installation manual provides a com-
plete listing of the points within the ACS Selection Groups and instructions on programming the panel for addressable annunciators.
ACS Selection
NOTE:
Annunciators configured for point annunciation:
• Do not respond to any status change that is not within its ACS Selection Group. This includes system alarm or system trouble.
• Do mask status changes for point number 1 of the start address selection.
• Do not respond to System Reset, Acknowledge, or Alarm Silence.
• Do not use the battery saving feature (100 mA battery load)
36
1
Group
1
Control Panel Status and Zones 1-56
2
Zones 57-99, NAC Ckts 1-4 and 16 Special Zones
3
Intelligent Modules 101 to 164
4
Intelligent Modules 201-264 (AFP-400 only)
5
Intelligent Modules 165-196 and 265-296 (AFP-400 only)
6
Detectors 101 to 164 on SLC loop 1
7
Detectors 201-264 on SLC loop 2 (AFP-400 only)
8
Detectors 165-196 and 265-296 (AFP-400 only)
9
Panel Output Circuit Modules (64 points)
A
Programmable annunciator group A; requires VeriFire™ 400 software to program
B
Programmable annunciator group B; requires VeriFire™ 400 software to program
* or 0
Annunciator Not Installed At Address
Table C.1 Zone and Point Mapping With AFP-300/AFP-400
Configuring Annunciators for the AFP-300/AFP-400
ACM-16AT and ACM-32A Function
Eight-Point Shift: Set switch "ON" to shift the control panel functions from the
first eight annunciator positions to expander positions 57-64. This shift can
only be set on an annunciator set for address "1".
Annunciator Display