Sensor Installation; Determining A Location - Siemens SITRANS F MASS 2100 Operating Instructions Manual

Coriolis flowmeters
Hide thumbs Also See for SITRANS F MASS 2100:
Table of Contents

Advertisement

4.2.2

Sensor installation

4.2.2.1

Determining a location

Electromagnetic fields
Do not install the flowmeter in the vicinity of strong electromagnetic fields, for example near
motors, variable frequency drives, transformers etc.
Upstream / downstream
• No pipe run requirements, that is straight inlet/outlet sections, are necessary.
• Avoid long drop lines downstream from the sensor to prevent process media separation
causing air / vapor bubbles in the tube (min. back pressure: 0.2 bar).
• Avoid installing the flowmeter immediately upstream of a free discharge in a drop line.
Location in the system
The optimum location in the system depends on the application:
• Liquid applications
Gas or vapor bubbles in the fluid may result in erroneous measurements, particularly in the
density measurement.
– Do not install the flowmeter at the highest point in the system, where bubbles will be
– Install the flowmeter in low pipeline sections, at the bottom of a U-section in the pipeline.
• Gas applications
Vapor condensation or oil traces in the gas may result in erroneous measurements.
– Do not install the flowmeter at the lowest point of the system.
– Install a filter.
SITRANS MASS 2100 & FC300 (FCT010/DSL)
Operating Instructions, 06/2020, A5E39788682-AB
CAUTION
trapped.
Figure 4-1
Liquid applications, wrong location with trapped air/gas
Figure 4-2
Gas applications, wrong location with trapped oil
Installing/mounting
4.2 Installation instructions
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans f fc300Fct010/dsl

Table of Contents