Powering on the Switch

This chapter describes how to connect the power modules in the chassis and to power on the switch.

Power Module Overview

You can install an AC power module in the chassis. Ensure all power connection wiring conforms to the rules
and regulations in the National Electrical Code (NEC) as well as local codes.
Each chassis has a power assembly shelf that supports the following number of power trays:
• Cisco 9808 chassis supports up to three power trays
Each power tray supports up to three AC power modules.
Note
Note
High-Voltage AC Power Supplies
HVAC power modules operate in the input range of 180 VAC to 305 VAC (nominal input level of 200 to
240 VAC, 277 VAC).
• NXK-HV-6.3KW20A-A: Each 6.3 KW, 20A power module can supply up to 6.3 KW to the power tray
• NXK-HV-6.3KW30A-A: Each 6.3 KW, 30A power module can supply up to 6.3 KW to the power tray
Power Module Overview, on page 37
Connect HVAC Power Supply to Power Source, on page 38
Power Supply Power Cord Specifications, on page 40
Use only one kind of power tray and power module in the chassis.
Use only the same capacity power module in the chassis. Do not mix different capacity power modules.
when it's supplied by two feeds (A and B). It can supply up to 3.15 KW with only one feed.
when it's supplied by two feeds (A and B). It can supply up to 4.8 KW with only one feed.