SSI:CODE (Signal coding)
Command
SSI:CODE
With this command the signal coding can be chosen. Take the data from the sensor's data sheet.
SSI:ERRBIT (Position of the "out of range" bit)
Command
SSI:ERRBIT
The position of the error bit will be defined by this parameter.
The appropriate data can be found in the sensor's data sheet. In case of no described error bit, the default
value is 0 (deactivation of the monitoring).
SSI:POL (Direction of the sensor signal)
Command
SSI_1:POL1
SSI_2:POL2
To reverse the working direction of the sensor, with this command the polarity can be changed.
SIGNAL (Type of input)
Command
SIGNAL_1:X
SIGNAL_2:X
This command can be used to change the type of input signal (voltages or current) and to define the direc-
tion of the signal. This command is available for the analogue feedback inputs.
OFF= Deactivation of the input.
Page 27 of 70
Parameters
X
x= GRAY|BIN
Parameter
X
x= 0... 31
Parameters
X
x= +|-
X
Parameter
X
x= OFF|U0-10| I4-20|
U10-0|I20-4
X
POS-124-U
Unit
Group
-
INPUT
Group
Unit
-
INPUT
Unit
Group
-
INPUT
Unit
Group
-
INPUT
24.01.2022