6.8.1.1 8Pin socket pin assignment
Assignment for inverters capable of both
Pin
charging and discharging
1
+12V
2
GND
3
DRM 1/5
4
DRM 2/6
5
DRM 3/7
6
DRM 4/8
7
RefGen
8
Com/DRM0
6.8.1.2 Method of asserting demand response modes
Socket Asserted by
Mode
shorting pins
DRM 0
7
8
Operate the disconnection device
DRM 1
3
8
Do not consume power
DRM 2
4
8
Do not consume at more than 50% of rated power
Do not consume at more than 75% of rated power
DRM 3
5
8
DRM 4
6
8
Increase power consumption
DRM 5
3
7
Do not generate power
DRM 6
4
7
Do not generate at more than 50% of rated power
DRM 7
5
7
Do not generate at more than 75% of rated power
Increase power generation (subject to constraints from
DRM 8
6
7
other active DRMs)
6.8.2 Inverter demand response modes-Power Control Interface(PCI) for EU
This series inverter has the function of demand response modes, We use 8Pin COM
PORTas Power Control Interface(PCI) for European models.
Excessive voltage can damage the inverter! External voltage of PCI
PORT don't over +5V.
WARNING
29
Requirement
RRCR
PCI Connector
6.8.2.1 8Pin socket pin assignment
Pin
Description
1
+12V
2
GND
3
Relay contact 1 input
4
Relay contact 2 input
5
Relay contact 3 input
6
Relay contact 4 input
7
GND
8
Not connected
6.8.2.2 The inverter is preconfigured to the following RRCR power levels
PCI Connector(SYS COM PORT)
Pin 3
Pin 4
Pin 5
Short circuit
with Pin7
Short circuit
with Pin7
Short circuit
with Pin7
Active power control and reactive power control are enabled separately

6.9 Earth Fault Alarm

The inverter complies with AS/NZS 5033.The installer does not need to perform any
additional actions, as this is already set up.When the Earth fault occurs,the Red LED will
light up.
The buzzer in the inverter will keep ringing unless the fault condition is cleared(This
function is only avilable for Australia and New Zealand).
Connect to RRCR
Not connected
K1 – Relay 1 output
K2 – Relay 1 output
K3 – Relay 1 output
K4 – Relay 1 output
Relays common node
Not connected
Active power
Cos(φ)
Pin 6
1
1
1
Short circuit
1
with Pin7
30