Installation
&
Operation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MID TL3-XH Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Growatt MID TL3-XH Series

  • Page 1 Installation & Growatt New Energy Operation Manual Download Manual Shenzhen Growatt New Energy Co., Ltd 4-13/F, Building A, Sino-German (Europe) Industrial Park, Hangcheng Ave, Bao’an District, Shenzhen, China +86 0755 2747 1942 service@ginverter.com www.ginverter.com GR-UM-320-A-00...
  • Page 2: Table Of Contents

    Contents 1 Notes on this manual 1.1 Validity 1.2 Intended audience 1.3 Symbols in this document 2 Safety 2.1 Product description and features 2.2 Qualified personnel 2.3 Safety instruction 3 Product overview 3.1 Appearance 3.2 Dimensions 3.3 Storage environment 4 Inspection upon delivery 5.1 Basic installation requirements 5 Installation 5.2 Wall-mounted installation...
  • Page 3 13 Troubleshooting 7 Commissioning 13.1 Error message 13.2 System warning 13.3 Systen error 14 Manufacturer Warranty 8 Working mode 8.1 Operating mode 8.2 Failure mode 8.3 Shutdown mode 15 Decommissioning 9 OLED display and the touch 15.1 Removing the inverter 9.1 Starting the inverter button 15.2 Packing the inverter...
  • Page 4: Notes On This Manual

    MID TL3-XH inverters manufactured by Shenzhen Growatt New Energy CAUTION Co.,Ltd.(hereinafter referred to as Growatt). Please read this manual carefully before using the product. Please note that the content of this manual is subject to change without notice.
  • Page 5: Safety 2

    1.3.3 Glossary 2.1.1 Product description Growatt series hybrid inverters are designed to convert the DC power generated by the Abbreviation for "Alternating Current” PV panels into three-phase AC power and export it to the grid or store the DC power in the batteries.
  • Page 6 The components in the inverter are live. Touching live components Ø 1.Please read this manual carefully before installation. Growatt shall not be liable for any can result in serious injury or death. damage caused by failure to follow the instructions and safety precautions specified in Do not open the inverter except the junction box.
  • Page 7: Product Overview 3

    Product overview 3 2.3.3 Operation Warnings 3.1 Appearance Ø Ensure all connectors are sealed and secured during operation. Ø Although designed to meet all safety requirements, some parts and surfaces of the inverter are still hot during operation. To reduce the risk of injury, do not touch the heat sink at the back of the PV-inverter or nearby surfaces while inverter is operating.
  • Page 8: Inspection Upon Delivery 4

    Inspection upon delivery 4 3.2 Dimensions Before unpacking the inverter, check the outer packing materials for any externally visible damage. After unpacking the inverter, check the scope of delivery for completeness. If the scope of delivery is incomplete or damaged, contact your dealer. Fig 3.2 Size and weight: Model...
  • Page 9: Basic Installation Requirements

    5 Installation 5.1 Basic installation requirements The wall on which the inverter is mounted must be sturdy and can withstand the Ø weight of the inverter for a long time (refer to the specifications in Chapter 17 for the weight of the inverter); The installation location should be suitable for the dimensions of the inverter;...
  • Page 10: Wall-Mounted Installation

    5.2 Wall-mounted installation 5.2.1 Installing the wall-mounting bracket For safety reason, avoid water pipes and power cables when drilling holes. Danger Fig 5.7 Dimensions of the wall-mounting bracket Fix the mounting bracket as the figure shows. The screws should not be fully flush when Fig 5.4 Installation Environment inserted.
  • Page 11: Security

    Electrical connection 6 6.1 Security High voltages in the conductive parts of a running inverter may cause electric shocks. Therefore, ensure that the inverter is disconnected from voltage sources and is not powered on before starting installation Danger Static electricity may damage the electronic components of the inverter.
  • Page 12: Dc Side Wiring

    2. Connect the AC cable to the corresponding AC terminal. Inverter model Switch specification MID 11KTL3-XH 25A(230/400V) MID 12KTL3-XH 25A(230/400V) MID 13KTL3-XH 30A(230/400V) MID 15KTL3-XH 30A(230/400V) MID 17KTL3-XH 35A(230/400V) Fig 6.3 Connecting the AC output power cable MID 20KTL3-XH 40A(230/400V) 3.Secure the protective cover onto the inverter and tighten the screw on the protective cover.
  • Page 13: Connecting The Bidirectional Dc/Dc Box

    Please ensure that the following conditions are met, otherwise it may cause negative DC input terminals of the inverter respectively. a fire hazard or damage the inverter. In this case, Growatt shall not be liable The maximum DC input current and voltage of the inverter shall not Ø...
  • Page 14: Connecting The Signal Cable

    6.4.2 Connecting the Bidirectional DC/DC Box 2.Connect the client-side to the port on the inverter and ensure that they are securely connected. Danger to life due to lethal voltages! Click! Before connecting the Bidirectional DC/DC Box, ensure that the Box is disconnected from any power supply.
  • Page 15: Active Power Control With A Smart Meter Or A Ripple Control Receiver

    Overcurrent withstand 20Imax for 0.5s damaged by lightning. WARNING In this case, Growatt shall not be liable for the consequence and the Pulse output 1 1000imp/kWh (default) damage is not covered by warranty. Pulse output 2 400imp/kWh 6.7 Active power control with a smart meter or a ripple control...
  • Page 16: Inverter Demand Response Modes (Drms)

    6.8 Inverter demand response modes (DRMs) 6.8.3 Using the Power Control Interface for EU models Inverters of this series feature the demand response modes and use a 16-pin socket as the DRMs connector. DRMs application description Ø Applicable to AS/NZS4777.2:2015 or Commission Regulation (EU) 2016/631.
  • Page 17: Gfci (Standard)

    1. When the grid goes down, the max. output power of a fully charged battery reaches 30kW. Wait until the screen is off. 2. Only professional personnel are allowed to configure the backup mode. To enable the backup mode, you need to purchase a backup box from Growatt.
  • Page 18: Commissioning

    If other error message is displayed, please refer to Section 13. If you encounter any technical problems, please contact Growatt support. 2. Turn on the circuit breaker or the switch between the inverter and the grid, the inverter 9.1 Starting the inverter...
  • Page 19 9.2 General settings 9.2.4 Setting the time Single tap to increase the number by one; double tap to confirm your setting. Set the 9.2.1 Setting the display language time as shown below: Multiple language options are available for this series inverter. Single tap to view different options;...
  • Page 20 9.3.1 Setting the export limitation parameter Single tap to view the options available or increase the number by one; double tap to confirm your setting. The -XH series inverters supports the export limitation function when working with an external power meter or CT. Users can configure the parameter on the OLED screen. Single tap to view the options available or increase the number by one;...
  • Page 21: Communication And Monitoring 10

    Communication and Monitoring 10 9.3.4 Setting the grid charging function 10.1 COM port Working with compatible batteries, the -XH series inverters can draw power from the This series of inverters provide four RS485 ports. You can monitor one or more inverters grid to charge the battery.
  • Page 22: Maintenance And Cleaning

    In some cases, you may heat sink to improve heat dissipation. need to contact Growatt for technical assistance. To provide you with the necessary support, please have the following information ready: 11.2 Checking the inverter...
  • Page 23 Warning 306 CT COM fault 2.If the error message persists, please contact contact Growatt support. Growatt support. 1.Check the polarity of the PV input terminals. 1.Check the connection of the communication Warning 210 PV Reversed 2.If the error message persists, please contact...
  • Page 24 Warning 404 EEPROM abnormal 2.If the error message persists, please contact Warning 503 Battery Voltage Low 2.Check the connection of the battery. Growatt support. 3.If the error message persists, please contact 1.Check the firmware version. Growatt support. DSP and COM firmware Warning 405 2.If the error message persists, please contact...
  • Page 25 Error 200 AFCI Fault current is overcurrent 2.Restart the inverter,If the error message 3.If the error message persists, please contact persists, please contact Growatt support. Growatt support. 1.Check whether the load exceeds the inverter 1.Restart the inverter. Leakage current too The off-grid Bus specification.
  • Page 26 Error 308 fault;pairing time 2.If the error message persists, please contact board and control 1.Restart the inverter. too long Growatt support. Error 410 panel sampling 2.If the error message persists, please contact battery voltage is Growatt support. 1.Check grid frequency and restart the inverter.
  • Page 27 AC PWM Bypass Error 423 2.If the error message persists, please contact permissible range; if so, replace the battery; if not, Protect Growatt support. Error 503 Battery voltage high restart the inverter. 2.If the error message persists, please contact 1.Restart the inverter.
  • Page 28: Decommissioning 15

    2. Restart the system,if the error message persists, Danger of burn injuries due to hot enclosure parts! please contact Growatt support. Wait 20 minutes before removing the inverter until the housing has cooled down. CAUTION 1.After shutdown, check the connection of the Abnormal communication cable.
  • Page 29: Eu Declaration Of Conformity

    •2014/35/EU Low Voltage Directive (LVD) •2014/30/EU Electromagnetic Compatibility Directive (EMC) Input data (DC) •2011/65/EU RoHS Directive and its amendment (EU)2015/863 Recommended Max. PV Shenzhen Growatt New Energy Co. Ltd confirms that the Growatt inverters and 22000W 24000W 26000W 30000W power(for module STC) accessories described in this document are in compliance with the above-mentioned.
  • Page 30 Model Model Specifications 11KTL3-XH 12KTL3-XH 13KTL3-XH 15KTL3-XH Specifications 11KTL3-XH 12KTL3-XH 15KTL3-XH 13KTL3-XH THDi <3% General data Dimensions (W / H / D) in AC grid connection type 3W+N+PE 579*433*217.5mm Efficiency Weight 29.5kg Max. efficiency 98.0% Operating temperature -25°C ... +60°C range (>45°CDerating) Euro-eta...
  • Page 31 Model Model Specifications 17KTL3-XH 20KTL3-XH 25KTL3-XH 30KTL3-XH Specifications 17KTL3-XH 20KTL3-XH 25KTL3-XH 30KTL3-XH Input data (DC) THDi <3% Recommended Max. PV AC grid connection type 3W+N+PE 34000W 40000W 50000W 60000W power (for module STC) Efficiency Max. DC voltage 1100V Max. efficiency 98.00% Start voltage 200V...
  • Page 32: Eu Certificate Of Compliance

    0~100% DC connection H4/MC4(OPT) If you have technical problems concerning our products, please contatc the Growatt AC connection Waterproof PG head + OT terminal or connect terminal Service Line. To provide you with the necessary support, please have the following...