General settings
Parameter
"Mode"
"P/Q Priority"
"Cos φ Minim-
um"
60
Range of val-
Description
ues
Reactive power mode selection option.
The following modes are described in the
subchapters.
Off
No reactive power is fed in.
Cos φ - Con-
Constant Cos φ.
stant Power
Factor
Q Absolute -
Constant reactive power in [Var].
Constant Re-
active Power
Q Relative -
Constant reactive power in percent [%] of
Constant Re-
S
.
n
active Power
Cos φ(P) -
Effective power-dependent Cos φ control.
Power depend-
ent Power
Factor Charac-
teristic
Q(P) - Power
Effective power-dependent reactive power
dependent Re-
control.
active Power
Characteristic
Q(U) - Voltage
Mains voltage dependent reactive power
dependent Re-
control.
active Power
Characteristic
Q Priority
When the maximum apparent power is
reached, the setting "Q Priority" leads to a
reduction of the effective power in favour
of reaching the reactive power specifica-
tion.
P Priority
The setting "P Priority" leads to a reduc-
tion of the reactive power in favour of
reaching the available effective power
when the maximum apparent power is
reached.
0 ‑ 1
Minimum cos φ, which together with the
maximum apparent power forms an addi-
tional limitation of the reactive power at
low effective power.