Parameter
Range of val-
ues
208 ‑ 311 [V]
"Activation
Threshold Over-
voltage"
0.01 ‑ 100 [%/
"Gradient Over-
voltage"
V]
"Calculation
P
max
Mode"
P
-P
m
P
max
P
-P
n
P
max
P
-P
m
"Active Grid
Off
Support"
On
0 ‑ 311 [V]
"Activation
Threshold Un-
dervoltage"
0 ‑ 100 [%/V]
"Gradient Un-
dervoltage"
Description
Mains voltage limit value
above which the power re-
duction takes place.
Gradient by which the ef-
fective power is reduced.
Example - conversion from
static to gradient:
Static s = 4 % → Gradient k
= 1/(0.04*230 V) =
10.9 %/V
=
Indicates the reference
power for calculating the
(k*dV)
m
power limit in the event of
overvoltage or under-
=
voltage.
(k*dV)
n
Reference power:
=
-
P
→ Momentary
m
(k*dV)
n
power when the
mains voltage limit
value is exceeded.
-
P
→ Nominal power
n
of the device.
Deactivates extended act-
ive mains support for
devices with battery.
Activates extended active
mains support for devices
with battery.
Mains voltage limit value
above which the power in-
crease takes place.
Gradient by which the ef-
fective power increases.
Example - conversion from
static to gradient:
Static s = 4 % → Gradient k
= 1/(0.04*230 V) =
10.9 %/V
Availability
Has no in-
fluence on
the follow-
ing setups:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020
39