Example 3
-
"P(f) Mode": On (with Hys-
teresis)
-
"Configuration Method":
Gradient
-
"Active Grid Support": Off
-
"Calculation Mode Under-
frequency": P
= P
max
P
(k*df)
n
-
"Calculation Mode Over-
frequency": P
= P
max
P
(k*df)
n
General power curve with overfrequency and underfrequency with hysteresis with gradients.
Description of the parameters
(1)
Momentary effective power when the
respective "Activation Threshold" is
reached: 60 % of P
(2)
"Gradient Underfrequency": 80 %/Hz
(3)
"Activation Threshold Underfre-
-
quency": 49.7 Hz
m
(4)
"Lower Deactivation Threshold Under-
frequency": 49.9 Hz
-
(5)
"Upper Deactivation Threshold Under-
m
frequency": 50.1 Hz
(6)
"Gradient Overfrequency": 60 %/Hz
(7)
"Activation Threshold Overfrequency":
50.3 Hz
(8)
"Lower Deactivation Threshold Over-
frequency": 49.9 Hz
(9)
"Upper Deactivation Threshold Over-
frequency": 50.1 Hz
(10)
"Deactivation Time": 30 s
(nominal power).
n
45