Fronius GEN24 Operating Instructions Manual page 61

Table of Contents

Advertisement

Depending on the selected mode, only the setting options in the respective
subchapter and these general settings have an effect.
const cos φ
Reactive power default defined by a constant cos φ. The function is limited by the
maximum apparent power and Cos φ minimum, the P/Q priority has no effect.
Parameter
Range of val-
ues
0 ‑ 1
"cos φ - Power
Factor"
"Direction / Ex-
citation"
Over-Excited
Under-Excited
0.01 s ‑ 60 s
"Time Constant
(τ)"
Description
Set value of Cos φ
The current direction corresponds to the
generator counter arrow system.
Over-excited operation = capacitive opera-
tion = reactive power is supplied = reactive
current is fed in lagging the active current.
Under-excited operation = inductive oper-
ation = reactive power is drawn = reactive
current is fed in ahead of the active cur-
rent.
Time constant (1 Tau) in seconds [s].
Whenever the set value is changed, this
new set value is not triggered abruptly, but
smoothly in accordance with a PT1 re-
sponse. The time constant describes how
quickly the new set value is reached. (After
three time constants the final value 95 %
is reached)
61