Parameter
"Return Gradi-
ent 2 Mode"
"Return Gradi-
ent 2"
Example 7
-
56
Range of val-
ues
Off
On
0.01 ‑ 100 [%/s
]
"Return Gradient 2 Mode"
= On
Description
Deactivates the use of
"Return Gradient 2". Rais-
ing the effective power
from the reduced value to
the device rated output
takes place according to
"Return Gradient 1".
Activates a different rate
of change at which the in-
verter increases the ef-
fective power from the ori-
ginal value to the device
nominal output. Raising
the effective power from
the original value to the
device rated output takes
place according to "Return
Gradient 2".
Rate of change at which
the inverter increases the
effective power from the
original value to the device
nominal output.
Description of the parameters
P
Actual power at the moment the limit
m
value is exceeded
P
Reduced power
red
(1)
"Gradient Overfrequency"
(2)
"Deactivation Time"
(3)
"Return Gradient 1"
(4)
"Return Gradient 2"
(5)
"Initial Delay"
At P
the grid frequency returns to the per-
red
missible range. After the end of the waiting
time (2), the power is increased to the initial
value P
with "Return Gradient 1". The power
m
is then increased to the device nominal out-
put P
with "Return Gradient 2" (4).
n