power and by "Cos φ Minimum". For the characteristic curves, the data points
must be entered in the X‑axis (effective power) and in the Y‑axis (Cos φ).
Point
1
2
64
Parameter
Range of val-
ues
0 % ‑ 100 %
"Active Power
(% of Nominal
Apparent
Power)"
0 ‑ 1
"cos φ - Power
Factor"
"Direction / Ex-
citation"
Under-Excited
Over-Excited
0 % ‑ 100 %
"Active Power
(% of Nominal
Apparent
Power)"
0 ‑ 1
"cos φ - Power
Factor"
"Direction / Ex-
citation"
Under-Excited
Over-Excited
Description
Effective power in percent
[%] related to the nominal ap-
parent power S
.
n
Set value of Cos φ.
The current direction corres-
ponds to the generator
counter arrow system.
Under-excited operation = in-
ductive operation = reactive
power is drawn = reactive cur-
rent is fed in ahead of the
active current.
Over-excited operation = ca-
pacitive operation = reactive
power is supplied = reactive
current is fed in lagging the
active current.
Effective power in percent
[%] related to the nominal ap-
parent power S
.
N
Set value of Cos φ.
The current direction corres-
ponds to the generator
counter arrow system.
Under-excited operation = in-
ductive operation = reactive
power is drawn = reactive cur-
rent is fed in ahead of the
active current.
Over-excited operation = ca-
pacitive operation = reactive
power is supplied = reactive
current is fed in lagging the
active current.