Fronius GEN24 Operating Instructions Manual page 46

Hide thumbs Also See for GEN24:
Table of Contents

Advertisement

Parameter
"Mode"
"Configuration
Method"
"Active Grid
Support"
46
Range of val-
Description
ues
Off
The function is deactiv-
ated.
On (with Hys-
Function is activated with
teresis)
hysteresis.
On (without
Function is activated
Hysteresis)
without hysteresis.
Gradient
For calculating the power
limitation depending on
the parameters "Gradient
Overfrequency" or "Gradi-
ent Underfrequency".
Stop - Fre-
The gradient is calculated
quency
automatically using the
parameters "Stop Fre-
quency - Overfrequency"
and "Power at Stop Fre-
quency - Overfrequency"
as well as "Stop Frequency
- Underfrequency" and
"Power at Stop Frequency
- Underfrequency".
Off
Deactivates extended act-
ive mains support for
devices with battery.
On
Activates extended active
mains support for devices
with battery.
Availability
In the fol-
lowing
setups "On
(without
Hysteresis)"
is not pos-
sible:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020
Has no in-
fluence on
the follow-
ing setups:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020