Power curve when "Activation Threshold Overvoltage" is exceeded.
Parameter
Range of val-
ues
200 ‑ 311 [V]
"Stop Voltage at
Undervoltage"
0 ‑ 100 [%]
"Power at Stop
Voltage - Under-
voltage"
Example: Setups AUS/NSZ
2020
-
"Mode": On (without hys-
teresis)
Description
Mains voltage limit value
up to which the charging
power of the battery is re-
duced. The gradient is cal-
culated automatically
from the parameters "Ac-
tivation Threshold Under-
voltage" and "Power at
Stop Voltage at Under-
voltage". The parameters
"Gradient Undervoltage"
and "Calculation Mode"
have no function.
Reference power when the
set mains voltage limit
value is reached. Only for
devices with battery in
charging mode.
Description of the parameters
(1)
"Activation Threshold Undervoltage":
210 V
(2)
"Stop at Voltage at Undervoltage":
200 V
(3)
"Power at Stop Voltage - Under-
voltage": 20 %
Availability
Used ex-
clusively in
the follow-
ing setups:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020
41