Parameter
"Lower Deactiv-
ation Threshold
Overfrequency"
"Transition Fre-
quency at Over-
frequency"
48
Range of val-
Description
ues
45 ‑ 66 [Hz]
Used when "Mode" is set to
"On (with Hysteresis)".
If this value is less than
the "Upper Deactivation
Threshold Overfrequency",
a frequency window res-
ults in which the grid fre-
quency must be located to
terminate the function. If
this value is greater than
or equal to the "Upper De-
activation Threshold Over-
frequency", it is not ap-
plied.
45 ‑ 66 [Hz]
Frequency at which the
device with active battery
reaches an output power
of 0 W. If the grid fre-
quency continues to rise,
energy is drawn from the
national grid and thus the
battery is charged. If there
is no battery in the system
or it is not active, this
parameter has no function
(behaviour as in example 3
- overfrequency).
Availability
Used ex-
clusively in
the follow-
ing setups:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020