Fronius GEN24 Operating Instructions Manual page 43

Hide thumbs Also See for GEN24:
Table of Contents

Advertisement

Once the grid frequency falls within the permitted frequency range again follow-
ing successful power reduction, return to the full power available takes place de-
pending on the country setup as follows:
-
Mode: "On (without Hysteresis)"
The inverter increases the power from the current reduced value to the ori-
ginal value in accordance with the same gradient used for power reduction.
-
Mode: "On (with Hysteresis)"
The inverter will not increase the power to the original value until the fre-
quency is back in the target value range for a specific length of time.
Example 1
-
"P(f) Mode": On (without
Hysteresis)
-
"Configuration Method":
Gradient
-
"Active Grid Support": Off
-
"Calculation Mode Under-
frequency": P
= P
max
P
(k*df)
n
-
"Calculation Mode Over-
frequency": P
= P
max
P
(k*df)
n
General power curve with overfrequency and underfrequency without hysteresis with gradients.
Description of the parameters
(1)
Momentary effective power when the
respective "Activation Threshold" is
reached: 60 % of P
(2)
"Gradient Underfrequency": 80 %/Hz -
Increase of output power without bat-
-
tery only possible if sufficient power
m
from PV generator is available and
manual power limitation is active. For
-
m
this purpose, the "Priority at Under-
frequency" parameter must be set to
"Priority on Frequency-dependent
Power Limitation".
(3)
"Activation Threshold Underfre-
quency": 49.7 Hz
(4)
"Gradient Overfrequency": 60%/Hz
(5)
"Activation Threshold Overfrequency":
50.3 Hz
(nominal power).
n
43