September 2022
6.9
Europe
6.9.1
I1 ATEX Intrinsic Safety
Certificate: Baseefa17ATEX062X
Standards:
Markings:
Special Condition for Safe Use (X):
1. The plastic mounting foot may present a potential electrostatic
ignition risk and must not the rubbed or cleaned with a dry cloth.
2. The equipment may be attached to process pipework at a
temperature of up to 200 °C as follows:
3. The enclosure may present a potential electrostatic ignition hazard
and must not be rubbed or cleaned with a dry cloth.
6.10
International
6.10.1 I7 IECEx Intrinsic Safety (IS)
Certificate: IECEx BAS 17.0047X
Standards: IEC 60079-0:2017 Edition 7.0, IEC 60079-11: 2011 Edition 6.0
Markings:
Special Condition for Safe Use (X):
1. The plastic mounting foot may present a potential electrostatic
ignition risk and must not the rubbed or cleaned with a dry cloth.
2. The equipment may be attached to process pipework at a
temperature of up to 200 °C as follows:
3. The enclosure may present a potential electrostatic ignition hazard
and must not be rubbed or cleaned with a dry cloth.
Quick Start Guide
EN IEC 60079-0:2018
EN 60079-11: 2012
II 1 G, Ex ia IIC T4...T2 Ga, Tamb = –50 °C to +75 °C, IP67
a. –50 °C ≤ Ta ≤ +120 °C for T4
b. –50 °C ≤ Ta ≤ +190 °C for T3
c. –50 °C ≤ Ta ≤ +200 °C for T2
Ex ia IIC T4...T2 Ga, T
a. –50 °C ≤ Ta ≤ +120 °C for T4
b. –50 °C ≤ Ta ≤ +190 °C for T3
c. –50 °C ≤ Ta ≤ +200 °C for T2
= –50 °C to +75 °C, IP67
amb
Quick Start Guide