Unit Is Leaking Water 机器漏水; Unit Is Running Properly, But The Sound Of The Unit Is Objectionable 机器运行,但声音不正常; High Pressure Switch Has Shut The Unit Down 高压开关已将机器关闭 - Wine Guardian D200 Installation, Operation And Maintenance Manual

Ducted wine cellar cooling systems
Table of Contents

Advertisement

Available languages

Available languages

Unit is leaking water 机器漏水
Possible Cause 可能的问题
杂物进入
Trap plugged
Condensate pan plugged 凝结水盆堵塞
Unit not level 机器不平
Unit is running properly, but the sound of the unit is objectionable 机器运
行,但声音不正常
Possible Cause 可能的问题
Noise is from airflow
声音来自气流
Noise is from unit
声音来自机器
High Pressure Switch has Shut the Unit Down 高压开关已将机器关闭
Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system.
This switch shuts the compressor and condenser down if the head pressure in the system is too
high. It is intended to protect the compressor. Restricted airflow through the condenser is the
most common reason for the pressure to become too high. This can be caused by dust covering
the filter or an obstruction blocking the airflow in the duct or grille.
每个酒卫机器有在高压制冷系统手动复位开关。如果系统水头压力过高此开关将关闭压
缩机和冷凝器。它的目的是保护压缩机。通过冷凝器的气流受限是压力变得过高的最常
见原因。这可能是由于灰尘覆盖过滤器或障碍物阻挡在管道或格栅气流。
Possible Cause 可能的问题
Head Pressure in unit is too high because
an obstruction is restricting air flow
机器压力过高,由于阻力限制了空气流动
Solution 解决方法
Clean trap 清除杂物
Remove blockage and clean 清除堵塞物并清
Level with shims 垫垫片
Solution 解决方法
Redirect airflow 重定向气流
Add baffles 添加挡板
Add insulated ductwork 增加绝缘管道
Add sound baffle between unit and occupied
space
增加声源和机器之间的隔离
解决方法
Solution
Remove the obstruction in the duct or grille or
clean the filter. Then restart the unit after
resetting the using the high pressure switch.
移除阻碍物,格栅,或者清洁线圈。然
后重启机器然后用高压开关复位。
87