Commissioning
8.1.2

Menu Levels

Fig. 5: Menu levels (excerpt)
8.1.3

Contents of the menu

Menu level 2 'Input'
Menu option
'Input type'
'Input unit'
Festo — VPPI-...-S1D — 2021-09a
Contents
'Analog'/'Digital'
[V/mA/]/[bar/kPa/psi]/
%
Description
Appears only for voltage variants. For current var-
iants, 'Input type' = 'Analog'.
– 'Analog': An analogue voltage / current value via
setpoint value (+) and setpoint value (-) deter-
mines the setpoint pressure.
– 'Digital': One of 8 setpoint values is specified via
three digital 24 V inputs. For this, the three inputs
are interpreted as a binary number with 3 bit.
The assignment is as follows:
– Setpoint value (+): DI0 or least significant bit
– Setpoint value (-): DI1
– Actual value output: DI2 or most significant bit
The value 000 means 0 bar and cannot be edited; the
remaining 7 values can be set in 'Input values'. There
is no actual value output in this mode.
Appears only if 'Input type' = 'Analog'.
Determines the unit in which the setpoint value is
displayed on the main screen.