15.4 Protection Parameter
Fuel Warn
Monitoring value of fuel level below
Level
which fuel level warning is generated.
Fuel Warn
Monitoring time for above.
Delay
Fuel Trip Level Monitoring value of fuel level below
which fuel level trip is generated.
Fuel Trip Delay Monitoring time for above.
LLOP Trip LevelMonitoring value of lube oil pressure
below which LLOP trip is generated.
LLOP Trip
Monitoring time for above.
Delay
HWT Trip LevelMonitoring value of water temperature
above which HET trip is generated.
HWT Trip DelayMonitoring time for above.
Oil Temp Trip Monitoring value of Oil temperature
above which Oil Temperature trip is
enabled.
This is only available if CAN Bus is
enabled.
Oil Temp Trip
Monitoring time for above.
Delay
Digital
Monitoring time for programmable digital
Input 1 Delay
input. Digital inputs are explained above.
Digital
Monitoring time for programmable digital
Input 2 Delay
input. Digital inputs are explained above.
Digital
Monitoring time for programmable digital
Input 3 Delay
input. Digital inputs are explained above.
15
Disabled*
11-80 %
10
1-100 Sec
15
10-80 %
Disabled*
10
1-100 Sec
1.0
0.4-8.5 Kg/cm2
Disabled*
5
1-100 Sec
90
40-249
Disabled*
5
1-100 Sec
100
40-250
Disabled*
5
1-100 Sec
5
1-100 Sec
5
1-100 Sec
5
1-100 Sec
Need help?