14.3 Mains Parameter
Over Voltage Max. Permissible Mains voltage, above this
the mains voltage is treated unhealthy and
Generator is started.
Under
Min. Permissible Mains voltage, below this
Voltage
the mains voltage is treated unhealthy and
Generator is started.
Mains Voltage
Duration for which Mains Over/Under
Delay
voltage condition can be tolerated before
starting the Generator.
Over
Max. Permissible Mains frequency, above
Frequency
this frequency the Mains is treated
unhealthy & Generator is started.
H
z
Mains U/F Min. permissible Mains frequency, below
this frequency the Mains is treated
H
z
unhealthy & Generator is started.
Mains Freq
Duration for which Mains Over/Under
Delay
frequency condition can be tolerated
before starting the Generator.
H
z
Voltage
Max. allowed voltage unbalance in
Unbalance
volt.
A
Voltage
Duration for which unbalance can be
Unbalance
allowed before starting the Generator. This
Delay
parameter is not available if above is set to
disabled.
A
270V
50-300V
180V
50-300V
10
1-999 Sec
65.0
40.0-69.9Hz
Disabled*
45.0
Disabled*
40.1-70.0Hz
5
1-999 Sec.
Disabled 10-99Volt
Disabled*
10
1-999Sec