Procom DGC-202 Series Operating Instructions Manual page 23

Advertisement

Parameter
Explanation of Parameter
Name on LCD
& Icon
System Config DGC202X provides complete flexibility in
system designing. This parameter defines
the system configuration in terms of the
mains and generator connections (Phases
1P or 3P)
Please note that the phases are defined
w.r.t to the input to the panel
CAN J1939 CAN Bus enable/disable.
DGC202X can be used engine with CAN
C A N
bus or without this bus.
Solenoid Type Pull to Start
Cranking command occurs after the
solenoid pre time set in generator
parameter. Fuel solenoid is kept pull till
the time engine is running. To stop engine
it is released
Pull to Stop
Fuel solenoid is pulled to stop the engine
for a pre-programmed duration.
LLOP Sensor
Select the installed sensor for LLOP.
Type
There are many built in sensors to choose
from. For sensors whose data is not in-
built User defined can be selected and the
sensor data programmed. Below twenty
parameters are for programming the User
defined sensors. If a in-built sensor is
selected the following twenty parameter
shall not be displayed
4-20Max
Max.Rangeof4-20mALLOPSensor. 40
Range
LLOP
R1 to R10 = Resistance Value
Sensor R1
V1 to V10 = Corresponding pressure
value.
These table are used when sensor type is
selected as user defined.
Factory Setting
AMF-M: 3P/G:3P
Disabled
Pull to stop
TYPE A
10
Setting Range
AMF-M: 3P/G:1P
AMF-M: 3P/G:3P
AMF-M: 1P/G:1P
Disabled*
Enabled
Pull to Stop
Pull to Start
User Defined
Type A
M&M
MNEPL
VE
TMTL
HUAFANG
TATA
GC(VDO)
GC(MURPHY)
4-20 ma
Disabled *
2-40
0-999