ICON
DESCRIPTION
Start Failed
Stop Failed
Engine High
Temperature
(HWT)
Low Lube Oil
Pressure(LLOP)
Under RPM
R P M
Over RPM
R P M
V Belt/Chg Alt
Low Fuel
Generator Under
Voltage
Generator Over
Voltage
Emergency Stop The emergency stop button has been depressed. This fail safe
LLOP Sensor
Open
HWT Sensor
Open
FUEL Sensor
Open
RWL
Oil Level
OilTemperature Oil Temperature.
Earth Fault
Canopy
Temperature
NOTES
The engine has not fired after the programmed number of starts
attempts
The controller has detected a condition that indicates that the
engine is running when it has been instructed to stop.
The controller detects that the engine coolant temperature has
exceeded the high engine temperature setting level and the Safety
On timer has expired.
The controller detects that the engine oil pressure has fallen below
the low oil pressure programmed level and the Safety On timer has
expired.
TheenginespeedhasfallenbelowtheprogrammedRPM
The engine speed has risen above the programmed RPM alarm
setting
The auxiliary charge alternator voltage is low
The level detected by the fuel level sensor is below the low fuel level
setting.
The generator output voltage has fallen below the programmed
setting after the Safety On timer has expired.
The generator output voltage has risen above the programmed
setting and the Timer has expired.
(normally closed to emergency stop) input and will immediately stop
the set should the signal be removed.
Oil pressure sensor has been detected as being open circuit.
HWT sensor has been detected as being open circuit.
Fuel sensor has been detected as being open circuit.
RWL fault.
Oil level fault.
Earth fault.
Canopy Temperature fault.