OPERATING INSTRUCTIONS DGC-7RR
PR OC OM
Auto
Man.
Test
Off
START MON GON STOP
Plot No. : 20-21, Industrial Estate,
Sector - 59, Phase-II, Faridabad (Haryana)
Ph.: 0129-4700400(10 Lines)
Email: pankajgupta@mrmprocom.com
Web: www.mrmprocom.com
DGC-7R
PROCOM
PROCOM
PROCOM
PROCOM
MRM
Fail to Stop
Fail to Start
LLOP
HWT/HCT
Canopy o C
DG Freq
Over speed
V-Belt
Crank
O/C
-
VIEW / PROGRAM
Pvt Ltd
Emergency
Low Fuel
DG Voltage
Battery
Solenoid
R
RESET

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DGC-7RR and is the answer not in the manual?

Questions and answers

Summary of Contents for Procom DGC-7RR

  • Page 1 OPERATING INSTRUCTIONS DGC-7RR PR OC OM DGC-7R Fail to Stop Emergency Fail to Start Auto LLOP HWT/HCT Low Fuel Canopy o C DG Freq Man. DG Voltage Over speed V-Belt Battery Test Crank Solenoid VIEW / PROGRAM START MON GON STOP...
  • Page 2 DGC-7R Digital Genset Controller Index Cat_DGC-7R-04-08-VERB1-0.doc Page 2/18...
  • Page 3 DGC-7R Digital Genset Controller Introduction Protection, Supervision Salient features Measurement & Display Annunciations Contacts Timers Switches Description Annunciations Description Lamp Test 10.0 Operating Mode 10.1 Auto Mode 10.2 Manual Mode 10.3 Off Mode 10.4 Test Mode 10.5 Remote Mode 11.0 Programming mode 11.1 Parameter Mode...
  • Page 4: Measurement & Display

    DGC-7R Digital Genset Controller Introduction • 16 Bit RISC, state of art, • All system parameters are user microcontroller based System. programmable • True RMS measurement of all • Suitable for all types of engines measured parameters with 1% accuracy including the one requiring choke.
  • Page 5 DGC-7R Digital Genset Controller • Fuel through Sensor Normally the display auto scrolls and displays a set of parameter for 10 seconds, but any time the Next key ( ) can be pressed to select the next parameter window. Annunciations DGC-7R is equipped with the following annunciations for system status and faults •...
  • Page 6: Switches Description

    DGC-7R Digital Genset Controller • V-Belt supervision timer (variable) • Hooter Reset Time(variable) • Delay between GCB to MCB switching (Variable) Switches Description DGC-7R has 12 switched are provided on its front panel. The table below describes the operation of these.
  • Page 7: Operating Mode

    DGC-7R Digital Genset Controller DG Freq This LED blinks when the engine is stopped on frequency fault. DG Vol This LED blinks when the engine is stopped on voltage fault. Over Speed This LED blinks when the engine is stopped on over speed fault. V-Belt This LED blinks when the engine is stopped on V-Belt fault.
  • Page 8: Off Mode

    DGC-7R Digital Genset Controller switch shall not operate if GCB contact is closed, to provide protection to generator. Once the generator is started the load can be switched to generator by pressing “GCB” switch or to mains by pressing MCB switch. At any given time, either of GCB or MCB can be operational. Attempt to switch on GCB while MCB is on will be ignored and vice versa.
  • Page 9: Common To All Models

    DGC-7R Digital Genset Controller Common to all Models Mains O/V Max. Permissible voltage, above 270V 80-300V this the voltage is treated unhealthy & Generator is started. Mains U/V Min. permissible voltage, below 180V 80-270V this the voltage is treated unhealthy &...
  • Page 10 DGC-7R Digital Genset Controller fault. Generator U/V Min. permissible Generator 180V 80-270V voltage, below this the Generator voltage is treated unhealthy & the Generator is stopped on voltage fault. Gen Sup Delay Duration for which generator 30Sec 0-999Sec Over/Under voltage condition can be tolerated before stopping the Generator.
  • Page 11 DGC-7R Digital Genset Controller Time allowed to run on no load before switching off Stop Sol On The time for which stop solenoid 30Sec 0-999Sec Time will be kept active while stopping the engine Fuel Level in % Fuel Level in %. Below this level 10-100% the fuel fault shall be acivated Fuel Delay...
  • Page 12 DGC-7R Digital Genset Controller voltage. If Auxiliary voltage is Disable* higher than this for 10sec the Battery LED starts blinking (only warning). DC U/V Min. permissible Auxiliary supply 10-40V voltage. If Auxiliary voltage is Disable* lower than this for 10sec the Battery LED starts blinking (only warning).
  • Page 13 DGC-7R Digital Genset Controller For models with Room Temperaure and BTS Voltage Measurement Any of (43) or (45) condition being satisfied shall start the generator For models with Canopy Temperaure Measurement Canopy Temp Max. permissible Canopy 20-99 temperature before the engine is shut down.
  • Page 14: Internal Faults

    DGC-7R Digital Genset Controller There are two categories of faults Internal Faults External faults 12.1 Internal Faults Internal faults are the faults, which do not need any external signals and are detected by the system itself. They are: Generator Fails to Start. Generator Voltage Unhealthy Generator Frequency Unhealthy.
  • Page 15: Terminal Description

    DGC-7R Digital Genset Controller a) Only one temperature measurement out of Room and Canopy can selected at a time Out of BTS Voltage, Room/Canopy Temperature and Current only 2 parameters can be selected at the same time. Single Phase unit can have provision for KW, PF and KWhr 15.0 Terminal description Terminal Number Description...
  • Page 16: Specifications

    DGC-7R Digital Genset Controller Current + Room/Canopy Temperature Temp+ Temp- 16.0 Specifications AC voltage withstand 330 VAC (Phase to neutral) Measurement Accuracy Surge 1.2/50Usec 2.5KV Battery Voltage Suitable for 12V/24 VDC System Min. voltage to power on Min Running Voltage after Power on Max.
  • Page 17 DGC-7R Digital Genset Controller Main R Phase Remote Start Main Main Y Phase Main B Phase Low Fuel Main Neutral Canopy Temp. 18 MCB Check Back Emergency 22 MCB NC Contact LLOP 23 MCB NC Contact Crank NO Not Connected Crank NO Not Connected Hooter...