Installation

WARNINGS:
• Installation shall only be performed by qualified personnel and in
accordance w ith local governing regulations.
• SITRANS Probe LU is to be used only in the manner outlined in this
manual, otherw ise protection provided by the equipment may be
impaired.
Notes:
Please refer to the device nameplate for approval information.
Ideally, mount SITRANS Probe LU so that the face of the transducer is at least
300 mm (1 ft) above the highest anticipated level.
M ounting Location
Recommendations:
Ambient temperature within –40 to +80 °C (–40 to +176 °F).
Easy access for viewing the display and programming via the handheld programmer.
An environment suitable to the housing rating and materials of construction.
Keep the sound path perpendicular to the material surface.
.
ambient temperature
surrounding enclosure
–40 to +80 °C (–40 to +176 °F)
process temperature
–40 to 85 °C (–40 to 185 °F)
7ML19985JB02
SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL
Doc Id: VM11
Active Date: 15/12/2006
flange adaptor (option)
customer-supplied
flange