Detailed Operation; Overview; Applications; Radiant Heating - heat-timer Genesis Installation And Operation Manual

Light commercial internet base control
Table of Contents

Advertisement

OVERVIEW

The Genesis Heat-Timer
®
control is design to operate a single boiler or valve in either a steam or hydronic heating application.
The Genesis Heat-Timer
®
control can provide outdoor reset where the heating output is automatically adjusted based on the outdoor
air temperature and the space temperature feedback.
The unique control of the Genesis Heat-Timer
with the ability to provide outdoor reset with space temperature feedback. The control also flexibility to control an ON/OFF boiler or
a modulating boiler (hydronic only) with a current voltage output. If the application is a valve, either a 2-way control valve in a steam
heating application or a 3-way mixing valve in a hydronic heating application, the Genesis Heat-Timer
output signal or a current voltage modulation signal to the valve actuator.
The Genesis Heat-Timer
®
control is supplied with 3 space temperature sensors that are wireless and provide feedback to the
controller on the current interior building temperature. This space temperature feedback is used to automatically adjust the
outdoor reset setting of the controller. Combining the benefits of outdoor reset with the space temperature feedback
the Genesis Heat-Timer
®
could potentially provide up to 30% in fuel efficiency while maintaining tenant comfort.
The Genesis Heat-Timer
®
control can be remotely accessed through the Internet using Heat Timer's web based program ICMS—
Internet Control Management System. Access to ICMS requires an active account with BuildingNet
access fee provides the account owner unlimited user access, which users can be given Full or Read Only rights of remote access to
®
the Genesis Heat-Timer
control.
ICMS also provides additional benefits and features other than remote access to the Genesis Heat-Timer
can create various alarm notifications via email and/or text, create and send various data reports based on the history of sensor data
and gather fuel and preventative maintenance information.

APPLICATIONS

RADIANT HEATING

The Genesis Heat-Timer
®
can control a 3-way mixing valve to regulate the temperature of the water entering the radiant tubing.

STEAM TO WATER HEAT-EXCHANGERS

The Genesis Heat-Timer
®
can control a 2-way steam valve to regulate the temperature of the heating water at a precise temperature.

BURNER CONTROL

The Genesis Heat-Timer
®
can control a burner on a steam or hot water boiler with either an ON/OFF enable signal or Current
Voltage Modulation signal (hydronic boiler only).

DISTRICT STEAM

The Genesis Heat-Timer
®
can control a 2-way control valve to regulate the volume of steam for precise heating.

STEAM HEATING

Whether the Genesis Heat-Timer
following heating applications:
One pipe steam—motorized valve or direct burner operation.
Two pipe steam—motorized valve or direct burner operation.
|
6
HEAT-TIMER CORP.
®
allows the installer the flexibility to choose between steam or hydronic heating, each
®
is controlling a boiler or a 2-way valve, the Genesis Heat-Timer
01

DETAILED OPERATION

®
will provide either a floating
®
and an annual access fee. This
®
control. The account user
®
can be applied to any of the
059705–00 REV. B

Advertisement

Table of Contents
loading

Table of Contents