HEATING SYSTEM MENU

Selections: Steam, Hot Water
Description:
Sets the type of application the Genesis Heat-Timer
STEAM or HOT WATER.
HEATING
SYSTEM—HOT WATER
Selections: On/Off Boiler
Curr Volt Boiler
Floating Valve
Curr Volt Valve
Description:
The Genesis Heat-Timer
any burner that is ON-OFF operation. The Genesis Heat-Timer
modulating input for a burner that requires a current voltage input such as 4–20mA,
0–10V, 2–10V and 0–5V.
For applications in which the Genesis Heat-Timer
®
Genesis Heat-Timer
can provide a SPDT output for valves with a floating actuator.
For valves with a proportional actuator, the Genesis Heat-Timer
voltage output of 4–20mA, 0–10V, 2–10V 1–5V and 0–5V.

MODULATING TYPE

Selections: 0–10V
2–10V
0–5V
1–5V
4–20mA
Description:
Select the current or voltage output signal to match the burner or
valve modulation. This selection is only available if the Heating System is Hot Water
Curr Volt Boiler or Curr Volt Valve.
059705–00 REV. B
17
STARTUP MENU—HOT WATER
®
Default: On/Off Boiler
®
can provide a simple ENABLE output for
®
can also provide a
®
controls a 3-way mixing valve, the
®
can provide a current
Default: Hot Water
will be controlling—
Default: 0–10V
HEATING SYSTEM
Steam
Hot Water
BACK
SAVE
HEATING SYSTEM
On/Off Boiler
Curr Volt Boiler
Floating Valve
Curr Volt Valve
BACK
SAVE
MODULATION TYPE
0-10v
2-10v
0-5v
1 -5v
4-20ma
BACK
SAVE
|