Boiler Or Direct/Indirect Water Heater Wiring; Domestic Hot Water Circulating Pump Wiring; Temperature Sensor Wiring; Supply Temperature Sensor - heat-timer DHW Energy Saver Installation And Operation Manual

Domestic hot water boiler or direct or indirect water heater and recirculating pump control with setback schedule
Table of Contents

Advertisement

Boiler or Direct/Indirect Water Heater Wiring

• T he DHW Energy Saver can control a single boiler. It turns on the
boiler/water heater whenever the supply temperature drops below the
Supply Set Point less the differential.
• J ust wire terminal 6 and 7 to the boiler TT terminals.
• H eat-Timer recommends the installation of a bypass switch for
maintenance and manual operation of the boiler/water heater.
• M ake sure to set the boiler limits higher than the DHW Energy Saver
Supply Set Point.

Domestic Hot Water Circulating Pump Wiring

• W hen the DHW Return is activated, the DHW Energy Saver will
energize the DHW circulating pump relay whenever the return
temperature drops below the Return Set Point less the differential
• T he DHW Energy Saver is equipped with a circulating pump relay
output. The relay can operate up to ⅛ HP pump at 120 VAC.
• T he Pump output relay does not source any power. A separate power
source is required for the pump.
• H eat-Timer recommends the installation of a bypass switch for
maintenance and manual operation of the pump.

Temperature Sensor Wiring

• O nly use a Standard Brass Tube sensor provided (HT #904250-00).
• T he sensor wires can be extended to 500 Ft by splicing it to
2-conductor shielded cable (#18/2 Shielded) (HT# 703001-01).
• C onnect the shield at the Platinum control circled terminal. The shield
MUST be cut at the sensor end.
• T he sensors must be inserted in ⅜"ID NPT well (HT# 904011-00 or
equivalent).

Supply Temperature Sensor

• T he Supply Temperature Sensor is required to be connected to the
Platinum Aux Temp 0 input terminals for the DHW Energy Saver to
control the boiler/water heater relay.
• T he Supply sensor must be installed in any of the boiler or water
heater aquastat fittings or no more than 10 Ft past the outlet of the
boiler/water heater, before any takeoffs.

Return Temperature Sensor

• T he return Temperature Sensor is included but optional. It should be
connected to the Platinum Aux Temp 1 input terminals for the DHW
Energy Saver to control the Pump relay.
• T he Return sensor should be installed less than 3 feet from the return
circulator on the return line.
DHW Energy Saver Installation and Configuration Manual
DHW Energy Saver
COM
16VAC
~
~
A GND B
1
2
3
4
5
DHW Energy Saver
COM
16VAC
~
~
A GND B
1
2
3
4
5
T
A1
OUT
TEMP
A2
A3
SHUTDOWN
A4
S
S
A5
PRESS
Bypass
4-20 mA
A6
+
Switch
(Optional)
A7
NETWORK
A8
A9
PROVE
A10
T
A11
AUX
TEMP 0
A12
A13
T
AUX
TEMP 1
A14
A15
T
AUX
TEMP 2
A16
A17
A18
Boiler
Pump
6
7
8
9
Bypass
Switch
(Optional)
TT
Boiler/Water
Heater
Boiler
Pump
6
7
8
9
DHW
Pump
L N
5

Advertisement