Eho Configuration Menu - Emerson Bettis SMART EHO G Series Service Instructions Manual

Double-acting actuator
Table of Contents

Advertisement

Section 8: Customizing Smart EHO Settings
September 2020
8.4

EHO Configuration Menu

NOTE:
Feedback Only Factory Set parameters cannot be changed. If an attempt is made to change
a Feedback Only Factory Set parameter, all LEDs on the LDM will blink for 2 seconds and the
parameter's value will remain unchanged.
Table 12.
SETUP
Enter Setup to set parameters of the SMART EHO.
See Section 8.1 for instructions to get into the EHO
Configuration Menu.
FIND
SMART EHO parameter quick search feature. See
section 8.1 for instructions on how to use the SMART
EHO quick search feature.
CHANGE SETTINGS
Allows user to make changes to the configuration
settings.
PASSCODE
User must enter a passcode to make any changes
to the parameters of the EHO.
VALVE CONTROL SETUP
Parameters related to controlling the actuator.
CONTROL MODE
Set the method of remote control.
See wiring diagram for remote control
configurations.
ACTUATOR CLOSE DIRECTION
The actuator closing direction.
Note: This will be factory set.
VALVE CLOSE DIRECTION
Configure the close and open position of the valve.
Note: This will be factory set.
LED COLOR
Change color of LEDs used to indicate actuator
status ( Open/Close/Opening/Closing).
ENCODER POSITION
Reports if the encoder is installed properly. If
the encoder is replaced or out of position, user
must check this parameter to determine if the
encoder has been set to the correct position.
Note: This is factory set.
56
Configuration Table (1)
MENU NAME
MAN-02-08-77-0714-EN Rev. 2
MENU
CONFIGURATION/
KEY
CALIBRATION VALUE
SU
Yes/No
Fn
Yes/No
CH
Yes/No
0 0 0 0
(Firmware after 2018)
PC
4 8 6 3
(Firmware before 2018)
CS
Yes/No
0 = 2 Wire
1 = 3 Wire
CO
2 = 4 Wire
3 = Analog
4 = Network
0 = Close CCW
Cd
1 = Close CW
0 = CW Valve
rt
1 = CCW Valve
0 = Run LED Red, Port LED
Green
LE
1 = Run LED Green, Port LED
Red
0 = Incorrect Position
EP
1 = Correct Position
Customizing Smart EHO Settings
Service Instructions
DEFAULT
ACTION
N/A
N/A
N/A
N/A
N/A
1 = 3 Wire
Feedback Only
Feedback Only
0 = Run LED
Red, Port LED
Green
Feedback Only

Advertisement

Table of Contents
loading

Table of Contents