Emerson Bettis SMART EHO G Series Service Instructions Manual page 71

Double-acting actuator
Table of Contents

Advertisement

Service Instructions
MAN-02-08-77-0714-EN Rev. 2
Table 22.
ESD CONFIGURATION
Configure the settings for the ESD controls.
Caution: This is a software ESD action. The software
ESD action will be initiated by the software of the
electronics. The hard wired ESD is independent from
the software ESD.
Customizing Smart EHO Settings
Configuration Table (11)
MENU NAME
ENABLE ESD FROM HARDWIRE
Provides indication if hardwire ESD is
enabled or disabled on the SMART EHO.
REDUNDANT ESD DELAY
Delay for triggering Redundant ESD if Hardwired
ESD fails or operates slowly
ENABLE SOFTWARE ESD FROM
LOST COMMUNICATION
Enable the SMART EHO to go to fail safe position if
Modbus communication link is lost for 5 seconds.
ENABLE ESD FROM HOST
Enable host system to provide a command to take
the Smart EHO to the fail safe position.
SOFTWARE ESD OVERRIDE LOCAL MODE
Enable host system to provide a command
to take the SMART EHO to the fail safe position.
SOFTWARE ESD ACTION
Configure the action to be taken if Enable ESD
from Lost Communication or Enable
ESD from Host is enabled.
SOFTWARE ESD OVERRIDE LOCAL MODE
Configure the SMART EHO to allow the host to
override LOCAL mode control with a software
ESD command.
WARNING: Enabling this would allow
the actuator to move during a software
ESD command.
SOFTWARE ESD OVERRIDE STOP MODE
Configure the SMART EHO to allow the host to
override STOP(OFF) mode control with a software
ESD command.
WARNING: Enabling this would allow the actuator
to move during a software ESD command.
SOFTWARE ESD OVERRIDE MOTOR
THERMAL ALARM
Configure the SMART EHO to allow the host to
override a Motor Thermal Alarm with a software
ESD command.
ESD OVERRIDE INHIBIT
Configure the Smart EHO to allow the host
to override Inhibit command with a software
ESD command.
Section 8: Customizing Smart EHO Settings
MENU
CONFIGURATION/
KEY
CALIBRATION VALUE
EC
Yes/No
0 = Disable
eH
1 = Enable
rE
0 to 60 seconds
0 = Disable
eC
1 = Enable
0 = Disable
eE
1 = Enable
0 = Disable
eE
1 = Enable
0 = Stop / Stay put
eA
1 = Open to Limit
2 = Close to Limit
0 = NO
eL
1 = YES
0 = NO
eS
1 = YES
0 = NO
et
1 = YES
0 = NO
ei
1 = YES
September 2020
DEFAULT
ACTION
n/a
1 = Enable
0 seconds
0 = Disable
0 = Disable
0 = Disable
Feedback Only
1 = YES
1 = YES
1 = YES
1 = YES
67