MAN-02-08-77-0714-EN Rev. 2
DISCRETE INPUT SETUP
Set the discrete input logic.
DISCRETE OUTPUT SETUP
Set the configurable output relays customer can
use to monitor for various parameters. Refer to
wiring diagram for relay terminal connection.
Customizing Smart EHO Settings
MENU NAME
FREQUENCY CONFIGURATION
The power supply frequency configuration.
Note: This will be factory set.
PHASE CONFIGURATION
The power supply phase configuration.
Note: This will be factory set.
HYDRAULIC LEAK ALARM DEBOUNCE COUNT
Set the maximum number of Valve Drift Alarms
allowed per hour. If Valve Drift Alarm Frequency
is more than the Hydraulic leak Alarm Debounce
Count, then the Hydraulic Leak Alarm will be
generated. If Valve Drift Alarm is less than the
Hydraulic Leak Alarm Debounce Count then
Hydraulic Leak Alarm will be automatically cleared.
LOW OIL ALARM ENABLE
If oil level sensor is present, then this parameter can
be used to Enable or Disable the Low Oil Alarm.
DISCRETE INPUT 1
Set if Discrete Input for OPEN command should be
Active on Close contact or Open Contact.
DISCRETE INPUT 2
Set if Discrete Input for CLOSE command should
be Active on Close contact or Open Contact.
DISCRETE INPUT 3
Set if Discrete Input for STOP/PST command should
be Active on Close contact or Open Contact.
DISCRETE INPUT 4
Set if Discrete Input for OPEN INHIBIT command
or OIL LEVEL SENSOR input should be Active on
Close contact or Open Contact.
DISCRETE INPUT 5
Set if Discrete Input for CLOSE INHIBIT command
should be Active on Close contact or Open Contact.
Section 8: Customizing Smart EHO Settings
MENU
CONFIGURATION/
KEY
CALIBRATION VALUE
0 = DC
1 = 50 Hz
Fc
2 = 60 Hz
3 = Not defined
0 = Single Phase
Pc
1 = Three Phase
dC
2 to 10
0 = Disable
LO
1 = Enable
di
Yes/No
0 = Active on Close
contact
d1
1 = Active on Open
contact
0 = Active on Close
contact
d2
1 = Active on Open
contact
0 = Active on Close
contact
d3
1 = Active on Open
contact
0 = Active on Close
contact
d4
1 = Active on Open
contact
0 = Active on Close
contact
d5
1 = Active on Open
contact
dO
Yes/No
September 2020
DEFAULT
ACTION
Feedback
Only
Feedback
Only
2
Feedback
Only
N/A
0 = Active
on Close
contact
0 = Active
on Close
contact
0 = Active
on Close
contact
0 = Active
on Close
contact
0 = Active
on Close
contact
N/A
59

Advertisement