Scb-10 Warning Codes; Fault Finding - DeDietrich HPI S Series User Manual

Reversible air/water "split inverter" heat pump
Table of Contents

Advertisement

Code
Message
A02.22
System flow warning
A02.55
Inval or miss SerNR
A02.80
Missing Cascade Ctrl
6.1.6

SCB-10 warning codes

Tab.26
List of warning codes linked to the SCB-10 PCB
Code
Message
A00.32
TOutside Open
A00.33
TOutside Closed
A00.34
TOutside Missing
A02.18
OBD Error
A02.37
Uncritic device lost
A10.45
RoomTempZoneA miss
A10.46
RoomTempZoneB miss
A10.47
RoomTempZoneC miss
A10.50
T_DHW top D miss
A10.54
Temp. Zone DHW miss.
A10.56
T_DHW Zone AUX miss
6.2

Fault finding

Tab.27
Problems
Probable causes
The radiators are cold. The heating setpoint tem­
perature is too low.
The heating mode is deac­
tivated.
The radiator valves are
closed.
The heat pump is not op­
erating.
The water pressure is too
low (< 1 bar).
7684505 - v04 - 10022022
Description
System water flow warning active
Invalid or missing device serial number
Missing Cascade controller
A warning code signals that the optimal operating conditions are not
fulfilled. The system continues to operate safely, but there is a risk of
shutdown if the situation continues to deteriorate.
If the situation improves, the warning code may disappear spontaneously.
When one of the codes below is displayed continuously, contact the
professional responsible for maintenance of the heat pump.
Description
Outside temperature sensor is either removed or measures a
temperature below range
Outside temperature sensor is either shorted or measures a
temperature above range
Outside temperature sensor was expected but not detected
Object Dictionary Error:
Uncritical device has been disconnected:
Measure of Room Temperature Zone A is missing
Measure of Room Temperature Zone B is missing
Measure of Room Temperature Zone C is missing
Domestic Hot Water temperature sensor top zone DHW is
missing
Temperature sensor Zone DHW is missing
Domestic Hot Water temperature sensor Zone AUX is missing
Corrections
Increase the value of the room temperature setpoint or, if a room unit is
connected, increase the temperature on it.
Activate the heating mode.
Open the valves on all radiators connected to the heating system.
Check that the heat pump is switched on.
Check the fuses and switches on the electrical installation.
Top up the system with water.
6 Troubleshooting
MIT-S
27