Scb-10 Blocking Codes - DeDietrich HPI S Series User Manual

Reversible air/water "split inverter" heat pump
Table of Contents

Advertisement

6 Troubleshooting
Code
Message
H00.33
TOutside Closed
H00.34
TOutside Missing
H00.47
HP flow sensor removed
or below range
H00.48
THp Flow Closed
H00.49
THp Flow Missing
H00.51
THp Return Open
H00.52
THp Return Closed
H00.57
T DHW Top Open
H00.58
T DHW Top Closed
H02.02
Wait Config Number
H02.03
Conf Error
H02.04
Parameter Error
H02.05
CSU CU mismatch
H02.07
Water Press Error
H02.09
Partial block
H02.10
Full Block
H02.23
System flow error
H02.25
ACI error
H02.36
Funct device lost
H02.37
Uncritic device lost
H02.60
Unsupported function
H06.01
HP Unit Failure
6.1.3

SCB-10 blocking codes

24
MIT-S
Description
Outside temperature sensor is either shorted or measures a temperature above range
Outside temperature sensor was expected but not detected
Heat pump flow temperature sensor is either removed or measures a temperature
below range
Heat pump flow temperature sensor is either shorted or measures a temperature
above range
Heat pump flow temperature sensor was expected but not detected
Heat pump return temperature sensor is either removed or measures a temperature
below range
Heat pump return temperature sensor is either shorted or measures a temperature
above range
Domestic Hot Water top temperature sensor is either removed or measures a
temperature below range
Domestic Hot Water top temperature sensor is either shorted or measures a
temperature above range
Waiting For Configuration Number
Configuration Error
Parameter Error
CSU does not match CU type
Water Pressure Error active
Check the hydraulic pressure in the heating circuit.
Partial blocking of the device recognized
BL input on the central unit PCB terminal block open
Full blocking of the device recognized
BL input on the central unit PCB terminal block open
System water flow error active
Flow problem
Insufficient flow: open a radiator valve.
The circuit is clogged:
Check that the filters are not obstructed and clean them if necessary.
Clean and flush the installation.
No circulation:
Check that the valves and thermostatic valves are open,
Check that the circulating pump is working,
Check the wiring,
Check the pump supply: if the pump does not work, replace it.
Titan Active System short-circuited or on an open circuit
Functional device has been disconnected
No communication between the central unit PCB and the additional circuit PCB
Uncritical device has been disconnected
No communication between the central unit PCB and the additional circuit PCB
The zone doesn't support the selected function
Heat Pump Unit Failure occured
Heat pump outdoor unit fault
A blocking code signals an anomaly affecting the heating system.
Several examples:
The system automatically attempts to correct the error (for example in
the event of a fault related to the flow rate).
The error is still present and the system functions in defect mode (for
example, in the event of a fault affecting the outdoor unit, the backup is
started up).
The system is shut down but automatically switches on again when the
error disappears.