Tab.1
Outdoor unit conditions of use
Limit operating temperatures
Water in heating mode
Outdoor air in heating mode
Water in cooling mode
Outdoor air in cooling mode
Tab.2
Heating mode: outside air temperature +7 °C, water temperature at the outlet +35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
Heat output
kW
Coefficient of perform
-
ance (COP)
Absorbed electrical
kWe
power
Nominal water flow
m
rate (ΔT = 5 K)
Tab.3
Heating mode: outside air temperature +2 °C, water temperature at the outlet +35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
Heat output
kW
Coefficient of perform
-
ance (COP)
Absorbed electrical
kWe
power
Tab.4
Cooling mode: outside air temperature +35 °C, water temperature at the outlet +7 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
Cooling output
kW
Energy efficiency ratio
-
(EER)
Absorbed electrical
kWe
power
Tab.5
Cooling mode: outdoor air temperature +35°C, water temperature at the outlet +18°C. Certified performances at full
load in accordance with EN 14511-2.
Measurement type
Unit
Cooling output
kW
Energy efficiency ratio
-
(EER)
Absorbed electrical
kWe
power
7684505 - v04 - 10022022
AWHP 4.5
AWHP 6
MR
MR-3
+18 °C /
+18 °C /
+55 °C
+60 °C
-15 °C /
-15 °C /
+35 °C
+35 °C
+7 °C / +25
+7 °C / +25
°C
°C
+10 °C /
+7 °C /
+46 °C
+46 °C
AWHP
AWHP 6
4.5 MR
MR-3
4.60
5.87
5.11
4.18
0.90
1.41
0.80
1.04
3
/h
AWHP
AWHP 6
4.5 MR
MR-3
3.47
3.74
3.97
3.30
0.88
1.11
AWHP
AWHP 6
4.5 MR
MR-3
4.52
4.50
2.77
2.71
1.63
1.66
AWHP
AWHP 6
4.5 MR
MR-3
6.39
7.41
2.98
2.90
2.14
2.56
AWHP 8
AWHP 11
MR-2
MR-2
AWHP 11
TR-2
+18 °C /
+18 °C /
+60 °C
+60 °C
-20 °C /
-20 °C /
+35 °C
+35 °C
+7 °C / +25
+7 °C / +25
°C
°C
+7 °C /
+7 °C /
+46 °C
+46 °C
AWHP 8
AWHP
AWHP
MR-2
11 MR-2
11 TR-2
8.26
10.56
10.56
4.27
4.18
4.18
1.93
2.53
2.53
1.47
1.88
1.88
AWHP 8
AWHP
AWHP
MR-2
11 MR-2
11 TR-2
5.93
10.19
10.19
3.12
3.20
3.20
1.90
3.19
3.19
AWHP 8
AWHP
AWHP
MR-2
11 MR-2
11 TR-2
6.65
9.90
9.90
3.00
2.77
2.77
2.22
3.57
3.57
AWHP 8
AWHP
AWHP
MR-2
11 MR-2
11 TR-2
10.29
15.49
15.49
3.15
3.48
3.48
3.27
4.45
4.45
3 Technical specifications
AWHP 16
AWHP 22
MR-2
TR–2
AWHP 16
TR-2
+18 °C /
+18 °C /
+60 °C
+60 °C
-20 °C /
-20 °C /
+35 °C
+35 °C
+7 °C / +25
+7 °C / +25
°C
°C
+7 °C /
+7 °C /
+46 °C
+46 °C
AWHP
AWHP
AWHP
16 MR-2
16 TR-2
22 TR–2
14.19
14.19
21.70
4.22
4.22
3.96
3.36
3.36
5.48
2.67
2.67
3.80
AWHP
AWHP
AWHP
16 MR-2
16 TR-2
22 TR–2
11.38
11.38
16.11
3.22
3.22
3.13
3.53
3.53
5.14
AWHP
AWHP
AWHP
16 MR-2
16 TR-2
22 TR–2
9.74
9.74
11.30
2.89
2.89
2.80
3.37
3.37
4.07
AWHP
AWHP
AWHP
16 MR-2
16 TR-2
22 TR–2
18.36
18.36
23.23
2.81
2.81
2.88
6.53
6.53
8.07
MIT-S
AWHP 27
TR–2
+18 °C /
+60 °C
-20 °C /
+35 °C
+7 °C / +25
°C
+7 °C /
+46 °C
AWHP
27 TR–2
24.40
3.80
6.42
4.20
AWHP
27 TR–2
14.70
3.13
4.70
AWHP
27 TR–2
13.20
2.82
4.69
AWHP
27 TR–2
23.52
2.85
8.25
9