4 Planning

Room temperature control
Radiant tube heating-systems must be equipped
with a temperature control.
Section heating is allowed without temperature
control.

Position of suspension

Suspension height
Radiant tubes must be positioned so that no one in
the radiation area is exposed to an extreme high
heat level. This is ensured when the minimum
suspension heights shown in the following table are
adhered to:
Nominal
Suspension height in m
thermal load in
[max. radiation intensity 200 W/m
kW - gross
[net]
A = horizontal
16.7 [15]
3.5 m
21.1 [19]
4.0 m
32.2 [29]
4.8 m
43.3 [39]
5.5 m
54.4 [49]
6.8 m
Tab 1:
Minimum suspension heights
Key:
A = Minimum height when hanging horizontally
B = Minimum height when hanging angled
a
Type
[cm]
[cm]
20S U
110
25S U
110
35S U
130
45S U
170
55S U
230
Tab 2:
Safe distances
Key:
a = Minimum radial safety distance [inside radiation area]
b = Minimum upper safety distance when hanging horizontally
c = Minimum upper safety distance when hanging angled
d = Minimum lateral distance to supply pipes outside radiation
area
]
2
B = angled [30°]
3.1 m
3.6 m
4.3 m
4.9 m
6.2 m
b
c
d
[cm]
[cm]
20
15
15
20
15
15
20
15
15
25
25
25
35
35
35
novoSchwank shape U
Distances to flammable materials in the
radiant area
Radiant tubes must be positioned so that the
surface temperature of:
 components with flammable materials,
 flammable equipment, stored flammable
materials
never rises above 85° C.
Fig. 3: Suspension heights and distances for horizontal
application
Fig. 4: Suspension heights and distances for angled application
Direction of radiation
Radiant tubes novoSchwank can be positioned
horizontal or at an angle [max. 30° from vertical].
For this purpose suspension steel chains and cables
are installed at the suspension brackets.
7