Reflector Elongation - Schwank novoSchwank D 20S U Technical Manual

Radiant tube heater
Table of Contents

Advertisement

novoSchwank shape U

Reflector elongation

Vertical elongation of reflectors b=415 mm for
thermal protection.
The numbers of reflector elongation [single sheets]
is depending on required protection [one side
both side, protection length] and the power of
the radiant heater.
Delivery scope
The required reflector elongation can be
compiled depending on the extent of necessary
protection out of the following basic elements:
 02676300 reflector elongation L= 3000 mm
 02676310 reflector elongation L= 3000 mm
End segment U [only for for end segment
heater shape U with turn around box]
 02676320 reflector elongation L= 1500mm
Assembly instruction
1. Complete assembling heater with reflectors
complete [see chapter 9, page 21-24].
2. Mount bolts with spacer sleeves and mounting
brackets A at required positions [Fig. 48].
3. If required fasten mounting bracket B to turn
around box by losing 4 lower hex. nuts M8,
placing mounting bracket on tube flanges and
fastening hex. nuts [Fig. 50].
4. Place reflector elongation C on mounting
brackets A and bolt them together with
reinforcement plates D [self-securing nut M8]
[Fig. 48].
5. Bolt reflector elongation loosely together at
overlapping by means of M8 bolt/nuts.
6. In case of one-sided load on bolts mount
additional mounting bracket E [Fig. 49].
7. If using mounting bracket B mount safety lock F
[Fig. 50].
In the case of heaters with end reflector

the last hanger at the burner side must be
placed at the junction of the reflector
and the end reflector.
50
A
C
Fig. 48: Mounting of reflector elongation on hanger
Fig. 49: Mounting of reflector elongation on first hanger with
additional bracket
F
Fig. 50: Mounting of reflector elongation on turn around box
with safety lock
D
E
B