Parameter IC 4000/1 and setting

The burner control unit IC 4000/1 is already factory
preset.
The parameters can be read out by the Schwank
Service Software IC 4000 [RS-485 interface board]
and if necessary to be changed.
Parameter selection and settings can made
manually direct at IC 4000/1 by the two push
buttons SW 2 and SW 3 and the 7-segment display.
For this, unscrew the lid of the IC 4000/1 burner
control.
After power supply IC 4000/1 following sequence is
shown on the 7-segment display:
1. segment test, all 7 segments light up
2. software version [two successive numbers]
3. burner control software: 1
Parameter Parameter name and
parameter value definitions
PP01
Setting Communication
0: No MODBUS control [e.g. SRT-1]
1: MODBUS contol by SchwankControl Touch
PP02
Drive Fan
0: Phase angle control driven
1: PWM driven
Tab 8: Parameter level IC 4000/1
novoSchwank shape U
Factory
Set
setting
range
1
0 - 1
0
0 -1
37