Schwank novoSchwank D 20S U Technical Manual page 12

Radiant tube heater
Table of Contents

Advertisement

novoSchwank shape U
Flexible exhaust system novoSchwank 20S U – 55S U [wall terminal], Type B23
- version stainless steel -
Stainless flexible pipe to avoid install
with sink.
Join parts of the wall terminal by
compression strong together!
All joints inside of the building tighten
securely with clamp fittings!
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.

The wall terminal is fastened to the
building wall with screws by means of
the integrated flange plate. The flange
plate supports and secures the wall
terminal.
Fig. 9: Flexible exhaust system novoSchwank 20S U – 55S U [wall terminal], version stainless steel
12
Please note the safety distance to
flammable materials:
single-wall exhaust pipe: 80 mm
-
double-wall exhaust pipe +
-
wall terminal: 0 mm

System certification tube heater
novoSchwank U with exhaust line system
Future ew
Future ew-flex
Future dw
[Schräder]
Following components are required for mounting
the wall terminal stainless steel version
[Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system wall terminal
DN 100/160
Article no. 12202210
:
CE 0432–CPD-219983 /
CE 0432–CPD-219952 /
CE 0432-CPD-219996