Appendix 2.5.2 Shield Treatment Of Cables - Mitsubishi Electric E70 Series Connection Manual

Hide thumbs Also See for E70 Series:
Table of Contents

Advertisement

MITSUBISHI CNC
Appendix 2 EMC Installation Guidelines

Appendix 2.5.2 Shield Treatment of Cables

Use shielded cables for the cables wired outside the panel.
Use a shield clamp within 10cm of the lead-out port from the panel. (Refer to "EMC Countermeasure Parts: Shield
Clamp Fitting".)
(1) DC power supply cable [F110/F070 cable]
Operation panel
Display unit
Operation panel
I/O unit
-
Use a shield clamp within 10cm from the panel's inlet/outlet.
-
When using a ferrite core, install it on both ends of the connected units.
-
Always install a ferrite core (Refer to "EMC Countermeasure Parts: Ferrite Core".) on the general-purpose
stabilized power supply. The ferrite core may not be required depending on the selected power supply.
(2) Remote I/O cable [FCUA-R211 cable]
Control panel
Control unit
-
Use a shield clamp within 10cm from the panel's inlet/outlet.
-
When using a ferrite core, install it on both ends of the connected units.
168
Shield clamp
Control panel
F110 cable
General-purpose
stabilized power supply
F070 cable
Ferrite core
Shield clamp
FCUA-R211 cable
Ferrite core
PD25
Control panel
Remote I/O unit