Stepper Motor Connections - Aerotech Ensemble LAB Hardware Manual

Table of Contents

Advertisement

Installation and Configuration

2.3.5.3. Stepper Motor Connections

The configuration shown in
effective motor voltage is half of the applied bus voltage. For example, an 80V motor bus supply is needed to
get 40V across the motor.
Stepper Motor Phasing
A stepper motor can be run with or without an encoder. If an encoder is not being used, phasing is not
necessary. With an encoder, test for proper motor phasing by running a positive motion command.
If there is a positive scaling factor (determined by the CountsPerUnit parameters) and the motor moves in a
clockwise direction, as viewed looking at the motor from the front mounting flange, the motor is phased
correctly. If the motor moves in a counterclockwise direction, swap the motor leads and re-run the
command.
Proper motor phasing is important because the end of travel (EOT) limit inputs are relative to motor rotation.
N O T E : If using standard Aerotech motors and cables, motor and encoder connection adjustments are
not required.
N O T E :  After the motor has been phased, use the ReverseMotionDirection parameter to change the dir-
ection of "positive" motion.
42
Figure 2-19
is an example of a typical stepper motor connection. In this case, the
To Backshell
22
10
ØA [Pins 11, 23]
23
11
ØB [Pins 12, 24]
24
12
25
13
Note the common connection
of A and B phases.
Figure 2-19:
Stepper Motor Configuration
ROTARY MOTOR
Motor Mounting
Flange (Front View)
POSITIVE MOTION
Figure 2-20:
Clockwise Motor Rotation
Chapter 2
Ensemble LAB Hardware Manual
Motor Frame
A
A'
B
Stepper
Motor
B'
Motor Shaft
www.aerotech.com

Advertisement

Table of Contents
loading

Table of Contents